Measuring Range:
:Temperature Activ sensor: range selectable Attention: max. measuring temperature is restricted by max. medium temperature (see Safety data)
: Setting range [°C] range [°F] Factory setting
: S0 -40°C to 60°C -40°F to 160°F
: S1 0°C to 50°C 40°F to 140°F
: S2 -15°C to 35°C 0°F to 100°F
: S3 -20°C to 80°C 0°F to 200°F Yes
:Absolute Humidity adjustable at the transducer: 0 to 50 g/m³ (default setting), 0 to 80 g/m³
:Enthalpy 0 to 85 kJ/kg
:Dew Point adjustable at the transducer: 40°F to 140°F [0°C to 50°C] (default setting), 0°F to 200°F [-20°C to 80°C]
Accuracy:
:Humidity ±2% between 10 to 90% RH @ 70°F [21°C]
:Temperature±0.9°F @ 77°F [±0.5°C @ 25°C]
Stability:<1%RH/yr @ 73℉ (23℃), 50% RH
Supply Voltage:15-24 VDC, ±10%, 0.4 W; 24 VAC, ±10%, 0.8 VA
Signal Output (Active Temperature):
:22DTH-51 DC 0-5V, DC 0-10V
:22DTH-53 4-20mA
:22DTH-55M DC 0-5V, DC 0-10V
:22DTH-56M DC 0-5V, DC 0-10V
Signal Output (Active Humidity):DC 0-5V, DC 0-10V
:22DTH-51x DC 0-5V, DC 0-10V
:22DTH-53x 4-20mA
:22DTH-55M DC 0-5V, DC 0-10V
:22DTH-56M DC 0-5V, DC 0-10V
Signal Output (Passive Temperature):
:22DTH-51MB PT1000
:22DTH-51ME Ni1000 (JCI)
:22DTH-51ML NTC10k2
:22DTH-51MM NTC10k3
:22DTH-51MQ NTC20k
:22DTH-530B PT1000
:22DTH-530E Ni1000 (JCI)
:22DTH-530L NTC10k2
:22DTH-530M NTC10k3
:22DTH-530Q NTC20k
Signal Output :
:Modbus 22DTH-55M
:BACnet 22DTH-56M
Sensing Technology:Polymer capacitive sensor with stainless steel wire mesh
Operating Humidity:0 to 100% RH non-condensing
Operating Temperature:-30°F to 160°F [-35°C to 70°C]
Enclosure: NEMA 4X/ IP65
Dimensions:2.88″ x 2.58″ x 5.5″
Approvals :ISO 9001, UL 2043, UL 50
Weight: 0.12 lbs
Warranty: 5 years