Accuracy:
Thermistor:±0.36℉, (±0.2℃)
Humidity:±2% RH, (10% to 90%) @ 25℃
Supply Voltage:
Sensor:15 to 18 VDC @9mA, (Supplied from the Communication Output Module)
Comm Module:20 to 30 VDC/AC, 25mA maximum, 1.7VA @ 30 VAC
Signal Output:Communication Module Volts 0-5 or 0-10VDC,10kΩ min Resistance 20K span Thermistor 10K-2 or 10K-3
Input: External dry contact connection (Closed = Occupied)
Output (3 maximum):
Volts:0-5 VDC or 0-10 VDC, Imax = 20 mA DA or RA (factory configured)
Reed Switch:0.5A @ 24 VDC
Resistance:20K span, Vmax = 15 VDC, DA or RA (factory configured)
Thermistor:10K-2, 10K-3[11K] (factory configured)
Communication:Polling system (All messages are confirming), Baud rate 1200 baud, Poll Rate 400 ms, Type FSK
Sensing Technology:
Sensor:Type II 10,000Ω thermistor
Humidity:Capacitive polymer
Visual Indication:
Power:Green LED (on = powered)
Communication:Blue LED (blinks during normal communication)
Occupied:Red LED (on = occupied request)
Indication OPT.::LCD, (Temp/Humd/Setpoint/Occupied), Window 2.5”x1.5”, Main digit 3.5 digits,0.6” high, ±99.9
Operating Humidity:0-95% RH Non-condensing
Operating Temperature:32° to 122℉ (0° to 50℃)
Enclosure Rating:Comm Module: UL94V-0, RoHS
Wiring:
Sensor: 2 wires, Up to 500ft, AWG gauge 22-14AWG, twist per foot 5 per ft preferred, Shielding Preferred, Wire spec typical Belden 9841, External sensor 22-18 AWG, TSP, shield grounded, 25' max
Comm Module:Comm. & PWR 2 wires to the sensor, 22-14 AWG, Power In 2 wires, 12-28 AWG, Output 2 wires per output,12-28 AWG, Override Input 2 wires, 16-30 AWG
Wiring Terminations:
Sensor:AWG gauge 22-14AWG Twist per foot 5 per ft preferred Shielding Preferred (not required) Wire spec typical Belden 9841, Up to 500 ft (new or exisitng)
Comm Module:
Communication:
and Power:22-14 AWG
Power In/Output:12-28 AWG (2wires per output)
Override Input:16-30 AWG
Enclosure: ABS Plastic, UL94V-0
Approvals: RoHS
Warranty: 1 year
: