Supply Voltage: 12-28 VDC
Configuration:(2) Two-wire loop powered
Output:4-20 mA
Accuracy:±1.5% + 0.015 x reading
Measurement Range:
RH:0 to 100%
Temperature:
Wall:-40° to 140℉ (-40° to 60℃)
Duct:-40° to 176℉ (-40° to 80℃)
Entity Parameters:Vmax: 28V; Imax: 100 mA; Ci: 1nF; Li: 0 mH
Operating Temperature:
Transmitter: -40° to 140℉ (-40° to 60℃)
Duct Probe:-40° to 240℉ (-40° to 120℃)
Operating Humidity:0% to 100% non-condensing
Wiring terminations:terminals (14-22 AWG)
Dimensions:
Wall:9.5″ H X 6.5″ W X 2.5″ D (24.2 x 16.4 x 6.2 cm)
Duct (base):4.5″ H x 6.5″ W x 2.5″ D (11.5 x 16.4 x 6.2 cm)
Probe (duct):6.7″ (17) long x 0.47″ (1.2) diameter with 6.5' (2m) whip
Approvals:FM approved, CSA
Weight:
Wall:2.8 lb (1.25 Kg)
Duct:3.1 lb (1.4 Kg)
Warranty:2 year