Honeywell Analytics Gas Detection Controller VA301C-DLC

Honeywell Analytics Gas Detection Controller

 

The Honeywell Analytics VA301C-DLC Gas Detection Controller provides continuous monitoring of up to 96 inputs/outputs, on three channels, at distances up to 2000'. Modbus communication channels are included. The VA301C-DLC is pre-programmed at the factory, but menu driven changes can be made in the field. The VA301C-DLC allows monitoring of an entire network and will initiate an alarm or ventilation activation upon detection of a gas. One model is available with datalogging. The VA301C-DLC Gas Detection Controller is designed to be used as part of a control system that helps to prevent the formation of a hazardous environment when properly installed and maintained.


Products
Filter:

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
301-AP ANNUNCIATOR PANEL FOR VA301C INFO1,827.001,461.60
301-C GAS DETECTION CONTROLLER In Stock3,196.002,556.80
301-C-DLC GAS DETECTION CONTROLLER W/ DATALOGGING INFO3,802.003,041.60
301-C-DLC-BIP GAS DETECTION CONTROLLER W/ DATALOGGING BACNET INFO6,316.005,052.80
301-R8 RELAY MODULE W/ 8 RELAYS INFO1,042.00833.60
420-I DIGITAL ANALOG OUTPUT CONVERTER INFO1,733.001,386.40

Accessories

No accessories found
Features
  • Full array of visual indicators and audible alarm
  • Multiple fully programmable alarm levels
  • Programmable time delays
  • Failure indicator
  • Up to 96 transmitters and relay modules
  • Up to 768 events
  • Up to 128 zoning groups
  • Graphic 122 x 32 dot-matrix display
  • Datalogging available
  • Programmable relay differential
Specifications

Supply Voltage:

VA301C-DLC:17-27 VAC @ 8.6 VA or 24-38 VDC @ 350 mA

VA301R: 17-27 VAC @ 8.6 VA or 24-38 VDC @ 250 mA

Relay Output: 5A, 30 VDC or 250 VAC (resistive load)

VA301C-DLC:4 DPDT relays (alarms/fault), buzzer

VA301R:8 DPDT relays

Relay Setpoint:Multiple with high and low setpoints

Alarm Auditory Levels [Db]:65 dba @3 ft (1m)

Alarm Time Delay:0, 30 sec, 45 sec, 1-99 minute before and after alarm

Network:Capacity: Up to 96 transmitters and 96 relay modules

Communication:Three Modbus zones

Distance To Transmitters:2000' (600m) maximum, 65 ft (20m) T-Tap, 130 ft (40m) total T-Tap, 2000 ft (600m) maximum

User Interface:Dot-matrix display and keypad

Visual Indication:Blinking Green LED: Normal operation Red LED: Alarm Level 1, 2, and 3 Blinking Amber LED: Signal Tx Blinking Green LED: Signal Rx Yellow LED: Failure

Operating Temperature:-4° to 122°F (-20° to 50°C)

Operating Humidity:0% to 95% RH (non-condensing)

Dimensions:

VA301C-DLC: 8.0" H x 11.0" W x 2.7" D (20.3 x 28.0 x 7.0 cm)

VA301R:8.0"H x 9.5"W x 2.5"D (20.3 x 24.4 x 5.7 cm)

Weight:

VA301C-DLC: 2.3 lb (1.0 Kg)

VA301R:3.0 lb (1.4 Kg)

Approvals:CSA

Warranty:1 year

Certifications