Supply Voltage:
301C-DLC:17-27 VAC @ 8.6 VA or 24-38 VDC @ 350 mA
301R:17-27 VAC @ 8.6 VA or 24-38 VDC @ 250 mA
Relay Output:5A, 30 VDC or 250 VAC (resistive load)
A301C-DLC:4 DPDT relays (alarms/fault), buzzer
301R:8 DPDT relays
Relay Setpoint:Multiple with high and low setpoints
Alarm Auditory Levels [Db]:65 dba @3 ft (1m)
Alarm Time Delay:0, 30 sec, 45 sec, 1-99 minute before and after alarm
Network:Capacity: Up to 96 transmitters and 96 relay modules
Communication:Three Modbus zones
Distance To Transmitters:2000' (600m) maximum, 65 ft (20m) T-Tap, 130 ft (40m) total T-Tap, 2000 ft (600m) maximum
User Interface:Dot-matrix display and keypad
Visual Indication:Blinking Green LED: Normal operation Red LED: Alarm Level 1, 2, and 3 Blinking Amber LED: Signal Tx Blinking Green LED: Signal Rx Yellow LED: Failure
Operating Temperature:-4° to 122°F (-20° to 50°C)
Operating Humidity:0% to 95% RH (non-condensing)
Dimensions:
301C-DLC:8.0" H x 11.0" W x 2.7" D (20.3 x 28.0 x 7.0 cm)
301R:8.0"H x 9.5"W x 2.5"D (20.3 x 24.4 x 5.7 cm)
Weight:
301C-DLC:2.3 lb (1.0 Kg)
301R:3.0 lb (1.4 Kg)
Approvals:CSA
Warranty:1 year