Honeywell Analytics Carbon Monoxide Transmitter TP1-M

Honeywell Analytics Carbon Monoxide Transmitter


The Honeywell Analytics Model TP1-M Carbon Monoxide Sensor features a two-wire, 4-20 mA output signal and two alarm outputs. This CO sensor is the first available zero-maintenance CO gas monitor with an electrochemical sensor. The carbon dioxide detection unit is ideal for building automation systems, BAS, and HVAC applications. It has a low initial cost and installs quickly and easily into a standard single-gang outlet box. It has a two to three-year operational life and never needs calibration. The Carbon Monoxide monitoring sensor is designed to be used as part of a control system. When properly installed and maintained, the sensor helps to prevent the formation of a hazardous environment. For more information on the proper application and use of this product please read "Environmental Safety Devices" in our technical reference section.


(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
TP1-M CO WALL 2-WIRE FLUSH MT SENSOR In Stock850.00680.00


No accessories found
  • 0-500 ppm CO range(non-adjustable)
  • High accuracy (5% of range) electrochemical industrial sensor
  • Two alarm levels (25 and 200 ppm)
  • Two wire, loop-powered 4-20 mA analog output
  • LED status/diagnostic indicator
  • Low power consumption, only 50 mA
  • Fits standard single-gang outlet box
  • Automatic, full function self-test performed daily
  • Unobtrusive design with rugged stainless steel screen
  • Two to three-year operational life

Supply Voltage:10-28 VDC @ 50 mA

Accuracy:±5% of full range

Signal Output:Two-wire, 4-20 mA @ 650Ω,Output signal fail modes Self-test fail 2 mA; Sensor expired 2 mA Overrange gas alarm 24 mA

Measurement Range:0-500 ppm

Life Expectancy:2-3 years (plus one-year shelf life)

Sensor Technology:Electrochemical


Visual Indication:Power on: On No power:Off Self-test fail: Fast flash (1 per 0.5 sec) Life ending: Slow flash (1 per 2.0 sec) provides one-month warning Life ended: Off

Alarm Contacts:250 mA @ 24 VDC max (transistor switch) 10% DIF

Wiring Terminations:18-22 AWG

Operating Temperature:32℉ to 104℉ (0℃ to 40℃)

Operating Humidity:15% to 90% noncondensing

Dimensions:2.56″H x 1.75″W x 1.36″D (6.5 x 4.5 x 3.5 cm)

Weight:0.42 lb (0.18 Kg)

Approvals:CSA IEC No. 1010 ANSI/ISA S82.01 CSEC C22.2 No. 1010 EMC Directive 89/336/EEC

Warranty:2 years