Senva TG UL Series wall and duct sensors can be ordered as individual sensors or as any dual combination of CO/NO2/Propane/Methane sensor in a shared enclosure.   

The analog output model features two outputs that support daisy chain wiring - multiple sensors may be used in a parallel sequence (0-10V) for cost-effective coverage of large areas. The unit can also act as a stand-alone controller, utilizing the relay for exhaust fan operation, or the output for direct control of a VFD. 

The BACnet/Modbus model supports BACnet MS/TP & Modbus network communication in one unit. Standard features include network auto-configuration, a programmable fan relay, LED indicators, integrated display, and audible alarm.



Products
Filter:

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
TGD-ACN-A TGUL, DUCT, ANALOG, CO/NO2INFO1,035.00517.50
TGD-ACN-AS TGUL, DUCT, ANALOG, CO/NO2 OPAQUEINFO1,005.00502.50
TGD-ACX-A TGUL, DUCT, ANALOG, COINFO777.00388.50
TGD-ACX-AS TGUL, DUCT, ANALOG, CO OPAQUEINFO777.00388.50
TGD-ANX-A TGUL, DUCT, ANALOG, NO2INFO863.00431.50
TGD-ANX-AS TGUL, DUCT, ANALOG, NO2 OPAQUEINFO838.00419.00
TGD-BCN-A TGUL, DUCT, BCNT/MDBUS, CO/NO2INFO1,208.00604.00
TGD-BCN-AS TGUL, DUCT, BCNT/MDBUS, CO/NO2 OPAQUEINFO1,173.00586.50
TGD-BCX-A TGUL, DUCT, BCNT/MDBUS, COINFO949.00474.50
TGD-BCX-AS TGUL, DUCT, BCNT/MDBUS, CO OPAQUEINFO922.00461.00
TGD-BNX-A TGUL, DUCT, BCNT/MDBUS, NO2INFO1,035.00517.50
TGD-BNX-AS TGUL, DUCT, BCNT/MDBUS, NO2 OPAQUEINFO1,005.00502.50
TGM-ACN-A TGUL, METAL, ANALOG, CO, NO2INFO1,208.00604.00
TGM-ACN-AS TG, METAL, ANALOG, CO/NO2, OPAQUEINFO1,208.00604.00
TGM-ACX-A TGUL, METAL, ANALOG, COINFO949.00474.50
TGM-ACX-AS TGUL, METAL, ANALOG, CO, OPAQUEINFO949.00474.50
TGM-ANX-A TGUL, METAL, ANALOG, NO2INFO1,067.00533.50
TGM-ANX-AS TGUL, METAL, ANALOG, NO2 OPAQUEINFO1,067.00533.50
TGM-BCN-A TGUL, METAL, RS485, CO, NO2INFO1,380.00690.00
TGM-BCN-AS TGUL, METAL, RS485, CO, NO2 OPAQUEINFO1,380.00690.00
TGM-BCX-A TGUL, METAL, RS485, COINFO1,122.00561.00
TGM-BCX-AS TGUL, METAL, RS485, CO OPAQUEINFO1,122.00561.00
TGM-BNX-A TGUL, METAL, RS485, NO2INFO1,208.00604.00
TGM-BNX-AS TGUL, METAL, RS485, NO2 OPAQUEINFO1,208.00604.00
TGW-ACN-A TGUL, WALL, ANALOG, CO, NO2In Stock1,035.00517.50
TGW-ACN-AS TGUL, WALL, ANALOG, CO, NO2 OPAQUEINFO1,035.00517.50
TGW-ACX-A TGUL, WALL, ANALOG, COINFO777.00388.50
TGW-ACX-AS TGUL, WALL, ANALOG, CO OPAQUEINFO777.00388.50
TGW-ANX-A TGUL, WALL, ANALOG, NO2INFO863.00431.50
TGW-ANX-AS TGUL, WALL, ANALOG, NO2 OPAQUEINFO838.00419.00
TGW-BCN CO NO2 WALL BACNET/MOD LCD RELAYIn Stock1,766.86883.43
TGW-BCN-A TGUL, WALL, RS485, CO, NO2In Stock1,208.00500.00
TGW-BCN-AS TGUL, WALL, RS485, CO, NO2 OPAQUEINFO1,208.00604.00
TGW-BCX-A TGUL, WALL, RS485, COINFO949.00474.50
TGW-BCX-AS TGUL, WALL, RS485, CO OPAQUEINFO949.00474.50
TGW-BNX-A TGUL, WALL, RS485, COINFO1,035.00517.50
TGW-BNX-AS TGUL, WALL, RS485, CO OPAQUEINFO1,035.00517.50

Accessories

No accessories found
Features
  • Cost-effective dual gas sensing and control 
  • Flexibility of analog output model 
  • Versatility with BACnet/Modbus model 
  • High reliability reduces callbacks 
  • Easy to install 
Specifications

Power Supply: 15-30VDC/24VAC(1), 4W max, 160mA max.

Analog Outputs: 2 programmable outputs: 0-10V (default), 0-5V, 1-5V and 4-20mA (menu selectable)  CO output scaling: 0-200ppm (default), 0-1000ppm (menu selectable)  NO2 output scaling: 0-10ppm (default), 0-30ppm (menu selectable)  Temperature output scaling: -20 to 85oC 

BACnet /Modbus: Protocol RS-485: BACnet MS/TP, Modbus RTU, Modbus ASCII  Baud Rates: 9600, 19200, 38400, 57600, 76800, 115200  

Fan Relay: Fan relay characteristics: N.C. 1A@24/30VDC (50/60Hz) (no mains connection)  CO fan relay setpoint: 25ppm (default), 0-1000 ppm (menu selectable)  NO2 fan relay setpoint: 1ppm (default), 0-30ppm (menu selectable)  

Alarm Relay (Analog model only)  : Alarm relay characteristics: N.C. 1A@24/30VDC (50/60Hz) (no mains connection)  CO alarm relay setpoint: 100ppm (default), 0-1000 ppm (menu selectable)  NO2 alarm relay setpoint: 3ppm (default), 0-30ppm (menu selectable) 

Display: 3-1/2 digit LCD: Indicates CO ppm, NO2 ppm (menu selectable)

LEDs: Green, Yellow, Red: Green = Normal, Yellow = Relay, Red = Alarm  

Audible Alarm Exposure : 85dB Piezo transducer: 30 minutes above alarm setpoint per UL2034 (menu selectable)

CO Sensor Performance: Type: Electrochemical  Accuracy: ±5% of default range(2) ±5%of reading above menu selectable) Resolution: 1ppm  Certications: UL2034 Listed Component  Life expectancy: >7 years  Coverage Area: 5000-7500 square feet  

NOSensor Performance: Type: Electrochemical  Accuracy: ±5% of default range(3) ±5% of default range(3) ±5%of reading above 20ppm  Resolution: 0.1ppm  Life expectancy: >7 years Coverage Area: 5000-7500 square feet 

Methane Sensor Performance: Type: Catalytic  Detection Range: 0-50% LEL (Lower Explosive Limit)  Accuracy: 5% of range  Resolution: 1%LEL  Life expectancy: >5 years  Coverage Area: 5000 square feet  

Propane Sensor Performance: Type: Catalytic  Detection Range: 0-50% LEL (Lower Explosive Limit)  Accuracy: 5% of range  Resolution: 1%LEL  Life expectancy: >5 years  Coverage Area: 5000-7500 square feet  

Operating Environment: Temperature, continuous: -20 to 50oC  Humidity: 15-95% continuous, 0-95% intermittent  Max Elevation: 2000m  

Enclosure (Wall & Duct): Material: ABS/Polycarbonate  Dimensions: 4.0”h x 4.4”w x 2.1”d  Conduit Opening: Tapped 1/2” NPT  Rating: IP20 

Enclosure (Metal): Material & Enclosure Rating: Powder-coated steel/acrylic, NEMA 3R  Dimensions: 5.0”h x 4.3”w x 2.25”d  Opening: Dual air vents on the bottom of the enclosure  Mounting: Pre-drilled for 2x4” electrical box  Rating: IP20 

Approvals: Compliance UL61010-1 Listed UL, cUL

 Warranty:  7 years

Certifications