Supply Voltage:18-30 VAC @ 0.7 VA, 50/60 Hz or 18-42 VDC @ 29 mA
Accuracy:
T8100/T8300:400-1250 ppm: 3% or 30 ppm, whichever is greater; 1250-2000 ppm: ±5% +30ppm,
T8200:10% or 75 ppm, whichever is greater;
Humidity:±2.5% RH (20 to 80% RH)
Temperature:±0.8% @ 72°F (22°C)
Signal Output:0-5V, 0-10V, or 4-20 mA (500 ohms ) selectable for CO2, humidity, or temperature (simultaneous current or voltage output for CO2)
Measurement Range:
CO2:0 to 2000 ppm
Humidity:0 to 99% RH (non condensing)
Temperature:32° to 122°F (0° to 50°C)
Relay Type:SPDT, 0.5 A @ 125 VAC, 1 A @ 24 VDC
Sensing Technology:
CO2:Non-dispersive infrared (NDIR)
Humidity:Capacitive polymer
Temperature:Passive: 10kΩ Type II thermistor
Warm up time:(CO2) 10 minutes
Display:Scrolling LCD
Response Time:5 seconds
Operating Temperature:32° to 122°F (0° to 50°C)
Operating Humidity:0% to 95% RH
Weight:1.0 lb (0.45 Kg)
Approvals:RoHS, CE
Warranty:1 year (lifetime on calibration)