Supply Voltage:18 to 30 VAC RMS, 50/60 Hz or 18 to 42 VDC, polarity protected.
Signal Output:0 to 5V or 0 to 10V (Factory Configured)
Power Consumption:Typical values (1.65 watts peak, 0.65 watts avg.@ 42 VDC)
Accuracy:±40 ppm +3% of reading @ 22℃ (72℉) when compared with a factory
Non-Linearity:<1% of full scale @ 22℃ (72℉)
Temperature Dependence:0.2% of full scale per ℃
Measurement Range:0-2000 ppm
Calibration Interval:None, uses ABC Logic (Automatic Background Calibration)
Warm Up Time:Two minutes (operational); 10 minutes to achieve maximum accuracy
Response Time:Three minutes typical for a 90% step change at low duct speeds
Pressure Dependence:0.13% of reading per mm of mercury
Wiring Terminations:Leads, Terminals
Operating Temperature:0℃ to 50℃ (32℉ to 122℉)
Operating Humidity:0% to 95% RH, noncondensing
Dimensions:
:Probe Length T8041 4.09″ (10.38 cm) / T8042 8.07″ (20.51 cm)
:Probe Diameter 1.24″ (3.15 cm)
:Junction Box Depth 1.58″ (4.02 cm)
:Junction Box H x L 3.05″ x 3.05″ (7.46 cm x 7.46 cm)
Weight:0.5 lb (0.23 Kg)
Approvals:CE EMC, RoHS Compliant
Warranty:1 year