Air Products & Controls Duct Smoke Detector SL-2000 Series

Air Products & Controls Duct Smoke Detector

 

The Air Products & Controls SL-2000 Series Duct Smoke Detectors provide early smoke detection and sense combustion products present in air moving through HVAC ducts. Designed for use in building automation systems, BAS, each duct smoke detector uses intake sampling tubes to gather air samples. These are sold separately. A standard length exhaust tube is provided with each detector. These devices are designed to prevent the recirculation of smoke in areas by the air handling systems, fans and blowers. Complete systems may be shut down in the event of smoke detection.


Products
Filter:

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
FASTUBE THREE 24 IN SAMPLING TUBE SL-2000 FOR 6 FTINFO40.1020.05
RT-3000-N DUCT SMOKE DETECTOR IONIZATION NEMA 4XIn Stock493.32246.66
RT-3000-P DUCT SMOKE DETECTOR PHOTOELECTRIC NEMA 4XIn Stock443.79221.89
SL-2000-N SMOKE DETECTOR DUCT IONIZATIONIn Stock321.56160.78
SL-2000-P SMOKE DETECTOR DUCT PHOTOELECTRICIn Stock311.16155.58
SMARTSTART-BAC-E MULTIFUNCTION TIMER/COUNTER KIT 120VINFO627.35313.68
SMARTSTART-HAC-E MULTIFUNCTION TIMER/COUNTER KIT 120V DISINFO697.05348.53
STN-1.0 SAMPLING TUBE SL-2000 6IN T TO 12INIn Stock13.626.81
STN-10.0 SAMPLING TUBE SL-2000 5FT TO 10FTIn Stock43.7021.85
STN-2.5 SAMPLING TUBE SL-2000 1FT TO 2.5FTINFO17.868.93
STN-5.0 SAMPLING TUBE SL-2000 2.5FT TO 5FTIn Stock26.4013.20
STS-10.0 10 FT. SAMPLING TUBEIn Stock36.7518.38
STS-2.5 2.5'FT SAMPLING TUBEIn Stock16.188.09
STS-5.0 5 FT. SAMPLING TUBEIn Stock21.4010.70
TG-2000 CAN OF SMOKE FOR SL-2000 SERIESINFO106.9153.46
WP-2000 NEMA 3R ENCLOSURE FOR SL-2000INFO275.27137.63

Accessories

No accessories found
Features
  • Low-flow technology, 100-4000 fpm
  • Universal voltage: 24 VAC, 24 VDC, 115 VAC, or 230 VAC
  • Two Form C and one Form A alarm contacts and one trouble contact
  • Interchangeable ″plug-in″ photoelectric or ionization heads
  • Compatible with building automation and fire alarm systems
  • Dust filtering included in detector head
  • Interconnect up to 30 detectors for common functions
  • Compatible with MS Series Remote Accessories
  • Cover removal trouble indication
  • Magnet test capability
  • Front or rear loading sampling tubes
  • Optional weatherproof enclosure
Specifications

Supply Voltage:(without accessories)

 :24 VAC @ 55 mA standby, 190 mA alarm

24 VDC @ 15 mA standby, 70 mA alarm :

115 VAC @ 16 mA standby, 32 mA alarm :

230 VAC @ 10 mA standby, 20 mA alarm:

Frequency:50/60 Hz

Relay Contacts:Alarm (2) SPDT, 10A, 115 VAC, resistive

Alarm (1) SPST-NO, 2A, 115 VAC, resistive :

Trouble (1) SPDT, 10A, 115 VAC, resistive:

Air Velocity:100-4000 fpm (0.5-20.3 mps)

Radioactive Element:Americium 241, 0.9 μCi

Operating Temperature:

SL-2000-N:32° to 158°F (0° to 70°C)

SL-2000-P:32° to 140°F (0° to 60°C)

Operating Humidity:10% to 85% RH non-condensing

Enclosure Rating:NEMA 1, Gray plastic back box, clear plastic cover

Dimensions:4.5"H x 13.5"L x 2.25"D (11.4 x 34.3 x 5.7 cm)

Weight:3.5 lb (1.6 Kg)

Approvals:

Warranty:3 year

Certifications