Gas and Specialty Sensors

CM6, GD6, TX-6-AM, TX-6-HS, TX-6-ND



Product Bar End
Product Bar End

CM6, GD6, TX-6-AM, TX-6-HS, TX-6-ND

Macurco Toxic and Combustible Gas Sensors CM6, GD6, TX-6-AM, TX-6-HS, TX-6-ND

Macurco Toxic and Combustible Gas Sensors

 

The Macurco™ CM6, GD6, TX-6-AM, TX-6-HS, TX-6-ND, RD-6, CD-6 & OX-6 Series are low voltage, dual relay detectors, controllers and transducers. Each device has selectable 4-20 mA output, buzzer and digital display options. It is an electronic detection system used to measure the concentration of various gases. The CM6 is a low level meter capable of displaying from 0-200 ppm of carbon monoxide. The GD6 is a low level meter capable of displaying from 0-50% L.E.L of Methane, Propane or Hydrogen.The TX-6-AM is a low level meter capable of displaying from 0-100 ppm of NH3 (Ammonia). The TX-6-ND is a low level meter capable of displaying from 0-20 ppm of NO2 (Nitrogen Dioxide). The TX-6-HS is a low level meter capable of displaying from 0-50 ppm of H2S (Hyrdogen Sulfide). Kele is the leading supplier of building automation products. When you need the right product, right now, count on Kele.


Products

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
CM-FCK CALIBRATION KIT INFO1,891.001,512.80
CM12 CO DETECTOR W/4-20MA 2 SELECTABLE RELAYS 120V INFO1,320.001,056.00
CM6 CO DETECTOR W/4-20MA 2 SELECTABLE RELAYS In Stock1,257.001,005.60
CM6-FCK CALIBRATION KIT-17L INFO1,500.001,200.00
CME1-FTG CALIBRATION GAS 500 PPM CO INFO231.00184.80
DVP-120 CNTRL PNL 120V 12 SNSR INPU 3 RELAYS In Stock3,900.003,120.00
DVP-120M CNTRL PNL 120V 87 SNSR INPU 3 RELAYS INFO4,300.003,440.00
GD12 COMB WALL MNT W/4-20MA W/2 RELAYS 120V INFO1,466.001,172.80
GD6 COMB WALL MNT W/4-20MA W/2 RELAYS GAS SENSOR In Stock1,396.001,116.80
MRS485 MODBUS ADAPTER INFO315.00252.00
OX12 COMB WALL MNT W/4-20MA W/2 RELAYS 120V INFO1,466.001,172.80
OX6 COMB WALL MNT W/4-20MA W/2 RELAYS INFO1,396.001,116.80
RD-12 R22 R134A R404A R410A WALL 4/20MA 2 RELAYS 120V INFO2,051.001,640.80
RD-6 R22 R134A R404A R410A WALL 4/20MA 2 RELAYS 24V INFO1,992.001,593.60
TX-12-AM NH3 WALL MNT W/4-20MA W/2 RELAYS 120V INFO2,051.001,640.80
TX-12-HS H2S WALL MNT W/4-20MA W/2 RELAYS 120V INFO1,948.001,558.40
TX-12-ND NO2 WALL MNT W/4-20MA W/2 RELAYS 120V INFO1,879.001,503.20
TX-6-AM NH3 WALL MNT W/4-20MA W/2 RELAYS INFO1,992.001,593.60
TX-6-HS H2S WALL MNT W/4-20MA W/2 RELAYS INFO1,879.001,503.20
TX-6-ND NO2 SENSOR In Stock1,879.001,503.20

Accessories

No accessories found
Features
  • Easy calibration
  • Selectable fan and alarm activation
  • Mounts on standard 4x4 electrical box
  • Internally supervised system
  • Easy functional verification
  • Adjustable setpoints
  • Digital display
Specifications

Supply Voltage:12 to 24 VAC @ 3 VA or 12 to 32 VDC @ 125 mA, reverse polarity protected

Accuracy:±5% of range

Supply Current:Stand by 23 mA @ 24 VDC

Fan relay 50 mA @ 24 VDC:

Both relays (alarm) 75 mA @ 24 VDC:

Signal Output:4-20 mA @ 900Ω

Output Range (4-20 mA):

CM-6:0-200 ppm

GD6:0-50% L.E.L Methane, Propane, Hydrogen

TX-6-AM:0-100 ppm NH3

TX-6-ND:0-20 ppm NO2

TX-6-HS:0-50 ppm H2S

RD-6:0-1,000PPM

OX-6:0-25% v/v

CD-6:0-2,000PPM

Life Expectancy:7+ years

Visual Indication:LED (1) Status (green)

Display 3 digit LED:

Buzzer:85 dba @ 4″(10cm)

Time Range: Fan and Alarm: relay minimum run time: selectable Off (default), 3, 5, 10 or 15 minutes

Relay Output:Fan: 5A, 240 VAC, pilot duty SPDT

 :Alarm: 0.5A @ 200Volts, 10 VA, (1 ppm DIF)

Time Delay:Fan and Alarm: Selectable at 0, 1, 3 (default), 5 and 10 minutes

Wiring Terminations:Plugs/terminals

Operating Temperature:0° to 125°F (-18° to 52°C)

Operating Humidity:10 to 90% RH

Enclosure Rating:NEMA 1

Dimensions: 4.5"W x 4.0"H x 2.125"D (11.4 x 10.2 x 5.4 cm)

Weight: 1.0 lbs (0.45 Kg)

Approvals: ETL Listed to UL 61010-1, CAN/CSA C22.2 No 61010-1

Warranty: 2 year

Certifications