Gas and Specialty Sensors

AGM-SZ



Product Bar End
Product Bar End

AGM-SZ

Bacharach Single Zone (tube) Ammonia Gas Monitor AGM-SZ

Bacharach Single Zone (tube) Ammonia Gas Monitor

 

The Bacharach AGM-SZ Series Single Zone(tube) Ammonia Gas Monitor is designed for single point monitoring of ammonia gas with a 1/4″ O.D. tube up to 50 ft (15.2 m) distance from measuring point to monitor. The unit features a digital display for local indication of current gas levels and peak value. Three adjustable alarm levels with relay output designate leak, spill, and evacuation concentrations. Gas alarms and system fault conditions are indicated by visual and audible alarms. The Model AGM-SZ provides a system fault relay output and a 4 to 20 mA output for integration with remote monitoring equipment or building management systems. The AGM-SZ Single Zone (tube) Ammonia Gas Monitor is designed to be used as part of a control system that helps to prevent the formation of a hazardous environment when properly installed and maintained.


Products
Filter:

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
3015-5047 NH3 FOUR ZONE AMMONIA GAS MONITOR INFO24,409.0019,527.20
3015-5048 NH3 EIGHT ZONE AMMONIA GAS MONITOR INFO26,418.0021,134.40
3015-5049 NH3 12 ZONE AMMONIA GAS MONITOR INFO28,420.0022,736.00
3015-5050 NH3 16 ZONE AMMONIA GAS MONITOR INFO30,426.0024,340.80
3015-5111 NH3 AMMONIA TUBING 500 FT INFO1,371.001,096.80
AGM-SZ NH3 SINGLE ZONE AMMONIA GAS MONITOR INFO7,500.006,000.00

Accessories

No accessories found
Features
  • Three alarm levels with SPDT alarm contacts
  • Self diagnostics verify operation
  • LED status indication
  • System fault alarm
  • 200 data point logging
  • 4-20 mA output signal
  • 50-foot sampling tube and end filter included
  • Audible and visual alarm indication
  • Local indication of current and peak gas levels
  • Alarm-silence button
  • NEMA 1
Specifications

Supply Voltage:100 to 240 VAC @ 21 VA, 50/60 Hz

Accuracy:±10 ppm from 25 to 100 ppm or ±10% reading from 100 to 10,000 ppm

Signal Output:3 alarm relays, 1 fault relay, 240 VAC, 3A, (5% DIF) and 4-20 mA @ 500Ω (non-isolated)

Sensitivity:25 ppm

Measurement Range:25-10,000 ppm

Gases Detected:Ammonia (NH3, R-717)

Sensing Technology:Single-pass, infrared non-dispersive

Coverage:1/4″ O.D. tube up to 50 ft (15m) from measuring point to monitor

Warm Up Time:15 minutes

Response Time:9 to 90 seconds depending on sample tube length

Operating Temperature:32° to 122°F (0° to 50°C)

Operating Humidity:5% to 90% RH non-condensing

Enclosure Rating:NEMA 1

Dimensions:7.7"H x 13.7"L x 3.6"D (19.6 x 34.8 x 9.1 cm)

Weight:10.0 lb (4.5 Kg)

Approvals:UL File #E212266, CSA, CE

Warranty:2 years