Gas and Specialty Sensors

6300 Series



Product Bar End
Product Bar End

6300 Series

Bacharach Toxic and Combustible Gas Detector 6300 Series

Bacharach Toxic and Combustible Gas Detector

 

The Bacharach 6300 Series or MGS-150 Gas Detector is a standalone micro-processor-based system for continuous, effective monitoring of toxic and combustible gases. The 6300 Series provides a 4-20 mA output in proportion to the level of gas present and relay output to activate additional horns, strobes, or ventilation systems. The modular design adds functionality. The unit features a built-in 85 dBA buzzer. the rugged polycarbonate housing is resistant to rust, corrosion, and dents. The 6300 Series Gas Detector is designed to be used as part of a control system that helps to prevent the formation of a hazardous environment when properly installed and maintained.


Products

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
6300-1019 NO2 WALL SENSOR 4-20 MA RELAY MGS-150 WO FITTINGIn Stock1,094.46612.90
6300-1101 R134A WALL SENSOR 4-20 MA RELAY MGS-150 WO FITTINGIn Stock472.26264.47
AG-0912-BR PG9 TO 1/2 IN NPT FITTINGINFO95.8853.69
EP-0709-BR PG7 TO PG9 BRASS FITTINGIn Stock8.935.00
NP07-BR PG7 NUTIn Stock3.832.14

Accessories

No accessories found
Features
  • Built-in 85 dBA buzzer
  • 4-20 mA, 0-5/10V. 1-5V or 2-10V and relay outputs
  • Wide variety of gases detected
  • Wall or duct mount
  • Easy installation, commissioning, and operation
  • LED status indication
  • Gases detected: Carbon monoxide (CO), Nitrogen dioxide (NO2-diesel exhaust),
  • Oxygen (O2), Hydrogen Sulfide (H2S), Methane (CH4),
  • Propane (C3H8), Carbon dioxide (CO2), R134A Refrigent
Specifications

Supply Voltage:24 VAC @ 1.9 VA, 50/60 Hz; 24 VDC @ 80 mA

Signal Output:4-20 mA @ 1000Ω, 0-5V, 0-10V, 1-5V or 2-10V

Measurement Range(alarm):

Methane, Propane:0-2000 ppm (1000 ppm)

CO,NH3:0-500 ppm (250 ppm)

NO2:0-10 ppm (4 ppm)

R134A, R410A:0-1000 ppm (500 ppm)

Oxygen:0-30% (19%)

Sensing Technology:

CO, NO2, O2: Electrochemical

NH3, R134A, R410A, Methane, Propane :Semiconductor

Calibration Interval:6 months

Life Expectancy:

CO, NO2, O2: 2-5 years

NH3, R134A, Methane, Propane :5-8 years

Visual Indication:Green LED: power Red Alarm

Alarm Relay Output:SPDT, 1 A @ 24 VAC/VDC (5% DIF)

Alarm Auditory Levels [Db]:85 dBA @ 10 ft (3m)

Operating Temperature:-4° to 122℉ (-20° to 50℃)

Operating Humidity:0 to 95% non-condensing

Dimensions:

Wall:3.4″H x 5.6″W x 2.1″D (8.6 x 14.2 x 5.3 cm)

Duct:5.1″H x 6.3″W x 3.5″D (13 x 16 x 9 cm)

Weight:

Wall:0.4 lb (0.2 Kg)

Duct:1.3 lb (0.6 Kg)

Approvals:CE

Warranty:1 year

Certifications