Supply Voltage:24 VDC ±10%
Accuracy: ± 1.0% of rate
Repeatability:± 0.15% of flow rate
Output Signal:2-wire, 4-20 mA @ 500Ω
Response Time:0.33 mS
Display:2-line alphanumeric with bar graph
Wiring Terminations:Screw terminals
Conduit Connection:3/4″ FNPT
Configuration:Factory pre-configuration required to assure application/product match: specify pipe size and material/schedule, fluid/gas type, operating pressure and temperatures, and minimum/maximum flow rates
Flow Turndown Ratio: Steam 10:1
: Gas 15:1 application dependent
: Liquid 15:1
Pipe Size Range:4″ to 60″ (100 to 1500 cm)
Turn Down:15:1
Installation: Install in straight pipe section with a minimum distance of 10 pipe diameters upstream and 5 pipe diameters downstream to any bend, obstruction or transition
Mounting: ANSI flanges standard
Media Compatibility:Liquid, non-volatile gases, or steam
Media Temperature Range:-65° to 425℉ (-54° to 218℃), other ranges special order
Maximum Pressure:>1000 psi (69 bar) for primary sensing elements; piping connections per applicable ANSI specs
Materials Of Construction:316L stainless steel wetted parts, Polyester powder coated aluminum housing
Operating Temperature:-4° to 170℉ (-20° to 75℃)
Enclosure Rating:NEMA 4X
Dimensions:Height 10.8″ (32.4 cm) from mounting flange to top of transmitter; insertion length depends on pipe size specified, force sensor locates in center of pipe
Weight:9 lb (4.1 Kg) maximum
Approvals:CE, FM
Warranty:2 years