Supply Voltage:12-42 VDC
Maximum Output Impedance:RL = (Vsupply - 12) * 43.33
Output Signal:2-wire, 4-20 mA, linear to flow
Wiring Terminations:Screw terminals inside housing
Conduit Connection:3/4" FNPT
Configuration:Factory pre-configuration required to assure application/product match: specify pipe size and material/schedule, fluid/gas type, operating pressure and temperatures, and minimum/maximum flow rates
Accuracy:± .05% for pipe sizes up to 8″, 1% to 2% for pipe sizes over 8″
Repeatability:± 0.15% of flow rate
Response Time:.002 to 0.1 seconds
Display:2-line alphanumeric with bar graph
Operating Temperature:-4° to 170℉ (-20° to 75℃)
Flow Range:19.6 gpm (4″ pipe) to 98,000 gpm (60″ pipe)
Velocity Range:Liquid flow: 1.5 fps (0.5 mps) minimum, 32 fps (9 mps) maximum
Pipe Size Range:4″ to 60″ (100 to 1500 cm)
Installation:Install in straight pipe section with a minimum distance of 10 pipe diameters upstream and 5 pipe diameters downstream to any bend, obstruction or transition
Mounting:ANSI flanges standard, other options available
Media Compatibility:Liquid, gas or steam
Media Temperature Range:-65° to 425℉ (-54° to 218℃), other ranges special order
Maximum Pressure:>1000 psi (69 bar) for primary sensing elements; piping connections per applicable ANSI specs
Materials Of Construction:Wetted parts: 304 and 316 stainless steel (or cast equivalent), Teflon® seals;
:Electronics housing: Polyester coated Aluminum
Enclosure Rating:NEMA 4X
Dimensions:Height 10.8″ (27.3 cm) from mounting flange to top of transmitter; insertion length depends on pipe size specified, target locates in center of pipe
Weight:9 lb (4.1 kg) maximum
Warranty:2 years