Supply Voltage:10-29 V DC
Supply Current:Max. 50 mA at 4000 ft/min
Output Signal:0-1 V (max. 1 mA)
:0-5 V (max. 1 mA)
:0-10 V2 (max. 1 mA)
Measurement Range:0-1000 ft/min
:0-2000 ft/min
:0-3000 ft/min
:0-4000 ft/min
Accuracy:Accuracy at 20℃ (68℉), 100...1000 ft./min, 40 ft/min + 3% of measured value
:45% RH, 1013 hPa (14.7 psi), 200...2000 ft/min, 60 ft/min + 4% of measured value
:200...3000 ft/min, 70 ft/min + 5% of measured value, 200...4000 ft/min, 80 ft/min + 6% of measured value
Response Time :typ. 4 sec or typ. 1 (at constant temperature)
Temperature Range :
Operation :-4° to 140℉ (-20° to 60℃)
Storage: -22° to 140℉ (-30° to 60℃)
Operating Range Humidity:5....95% rh (non-condensing)
Connection:
Cable version:1.6 ft, 6.6 ft cable, PVC, temperature-flexible, AWG 23 with ferrules
Electromagnetic compatibility:EN61326-1
: EN61326-2-3
Material / protection class:Polycarbonate / IP50 (probe head); IP54 (housing)
Approvals:CE
Warranty:1 year
Note: The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-fold standard deviation). The tolerance was calculated in accordance with EA-4/02 following the GUM (Guide to the Expression of Uncertainty in Measurement).: