The Badger Meter 310 Series programmable analog flow transmitter is a loop-powered device that converts the signal from a 200 or 4000 Series flow sensor into a linear 4-20 mA signal. Indispensable in Building Automation Systems, BAS, and HVAC applications, this flow transmitter features an integral, adjustable electronic filter that dampens the analog output for smooth, stable operation. The microprocessor-based 310 Series is configured from a computer, allowing it to be ordered pre-configured, or it can be field-configured. One Model A301-20 programming kit will configure all 310 Series transmitters.


Products

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
310-00 PROGRAMMABLE ANALOG FLOW TRANS In Stock585.78468.62
310-00-XR PROGRAM ANALOG FLOW TRANS CAL In Stock678.81543.05
310-01 TRANSMITTER/NEMA 4X ENCLOSURE In Stock807.82646.26
310-01-XR TRANS/NEMA 4X ENCLOSURE CALIB In Stock937.88750.30
310-02 TRANSMITER IN METAL ENCLOSURE INFO721.20576.96
310-02-XR TRANS. IN METAL ENCLOSURE CALI In Stock820.80656.64
310-03 TRANSMITTER IN PLASTIC ENCLOSU In Stock749.96599.97
310-03-XR TRANS IN PLASTIC ENCLOSURE CAL In Stock856.28685.02
310-04 TRANSMITTER W/DIN RAIL MOUNT In Stock651.32521.06
310-04-XR TRANS W/DIN RAIL MOUNT CALIBRA In Stock742.72594.18
840134-0002 USB TO DIC PROGRAMMING KIT In Stock451.26361.01
A301-20 PROGRAMMING KIT (PROGRAMMING CABLE & SOFTWARE) INFO1,434.071,147.26

Accessories

No accessories found
Features
  • 4-20 mA loop powered
  • Compact size
  • Computer programmable
  • Electronic signal dampening
Specifications

Supply Voltage:Loop powered, 9-35 VDC

Accuracy:±0.04% of reading over entire span

Input Signal:0.4 to 10 kHz, unscaled raw pulses from Data Industrial flow sensor, or sine wave

Output Signal:4-20 mA, 2-wire

Maximum Output Impedance:750Ω @ 24 VDC

Configuration:A301-20 programming kit (order separately) cable connects to DIC communication port and DB9 COM port on a computer. Transmitter must be loop-powered for programming (9-24 VDC will work)

Response Time:Varies with filter, typically 1 second 10% to 90% step response

Operating Temperature:-20° to 158℉ (-29° to 70℃)

Mounting:

 :310-00 Surface mount, transmitter only

 :310-01 Surface mount, in NEMA 4X enclosure

 :310-02 Surface mount, in metal enclosure

 :310-03 Surface mount, in plastic enclosure

 :310-04 DIN rail mount, with clips

Dimensions:

 :310-00, -04 1.8″H x 3.7″W x 1.5″D (4.4 x 9.3 x 3.8 cm)

 :310-01, -02, -03 2.8″H x 4.5″W x 2.0″D (7.1 x 11.3 x 5.1 cm)

Warranty:1 year