Supply Voltage:20 to 30 VAC, 50/60 Hz
Supply VA:2 VA
Display:Two-line backlit LCD
Controls:Five menu-driven buttons: up, down, menu, no, yes/scroll
Thermostat Type:7-day programmable and non-programmable models
Optimal Start:Progressive recovery enable/disable
Heat Pump High/Lo:Outside air lockout (emergency heating/compressor heating)
Stages Available:1H/1C, 2H/2C, (3H/2C heat pump) 2H/2C + proportional mixed air economizer
Memory (schedule):Permanent, EEPROM
Clock:Six-hour power-fail retention
System Switching:Off/Auto/Cool/Heat
Fan Switching:On-continuous
:Auto-on demand
:Smart-(on/occupied, off/unoccupied)
Control Accuracy :±0.9°F, (± 0.5°C) at 70°F (21°C)
Setpoint Range:
:Heating 40° to 90°F (4.5° to 32°C)
:Cooling 54° to 100°F (12° to 37.5°C)
Setpoint High/Low Limits :Individually-adjustable heating / cooling
Remote Sensor :
:Room Sensor Room Sensor input auto-detected 10K Type 2 thermistors
:Outside Air Outside air input auto-detected 10K Type 2 thermistors
:Mixed Air Mixed air input auto-detected (economizer model only) 10K Type 2 thermistors
Ancillary Inputs:Two dry-contact digital inputs, applied for:
:Service/status reminders
:Filter alarm
:Night setback clock
:Remote occupied override timer
Control Output:1A relays, 30 VAC, SPST, 3A surge maximum
Auxiliary Contact Output:1A relay, 30 VAC, SPDT, follows occupied schedule
Mixed Air Output:Proportional 0-10 VDC, 2KΩ minimum impedance (economizer model only)
Control Type:Proportional plus integral
Dead Band:Adjustable 2° to 4°F (1° to 2°C)
Outside Air Lockout Limits:
:Heating 15° to 120°F (26° to 49°C), 5° increments
:Cooling -40° to 95°F (-40° to 35°C), 5° increments
:Low Limit Protection Enable/disable, heating on at 47°F (5.5°C)
Power-up Delay:Adjustable 10 to 120 seconds
Keypad Lockout:3 levels, (full, none, partial)
Cycles Per Hour:Adjustable, heating 3-8; cooling, 3-4
Display Offset:Adjustable ± 5°F, (±2.5C), 1°F increments
LED Indicators :Three green “on” (fan, cooling, heating)
Wiring:18 AWG maximum, 22 AWG recommended
Mounting:Standard vertical 2" x 4" box
Enclosure:UL FR1 flame retardant plastic
Color:White
Operating Temperature:32°F to 122°F (0° to 50°C)
Operating Humidity:0 to 95% RH (non-condensing)
Dimensions:4.94"H x 3.38"W x 1.13"D
:(12.5 x 8.6 x 2.9 cm)
Weight:0.75 lb (0.34 kg)
Approvals:UL, cUL, File #E234137, CE
RoHS Statement:Yes
Warranty:1 year