Q. I have installed several RLD-5 Refrigerant Leak Detectors. Is there a simple way to verify their operation?

A. Yes! To verify operation of your RLD-5 (or RLD-134A) Refrigerant Leak Detectors, simply apply a small amount of alcohol to a cotton swab and hold it below the sensing element. This should cause an increase in the analog output signal.