Relays and Contactors

FL1 Series



Product Bar End
Product Bar End

FL1 Series

IDEC Multifunction Electronic Timer/Counter FL1 Series

IDEC Multifunction Electronic Timer/Counter

 

The FL1 Series multifunction electronic timers are DIN rail or surface mounted adjustable time delay relays. The FL1 Series can be used with expansion modules to extend input/output capabilities or use the LonWorks communication module for interfacing with the network. An external text display can be used to monitor, view, and troubleshoot from outside of the panel. Models are available in a variety of supply voltages and with or without a display.


Products
Filter:

(Wholesale customers, log in for your special pricing)

QtyModelDescriptionIn StockList PriceInternet Price
FL1B-B12RCE SMART RELAY INFO419.23335.38
FL1B-CL1C12 LONWORKS MODULE INFO1,176.04940.83
FL1B-J2B2 ANALOG INPUT MODULE INFO398.16318.53
FL1B-M08C2R2 COMBINATION I/O MODULE INFO278.73222.98
FL1B-M08D2R2 COMBINATION I/O MODULE INFO278.73222.98
FL1E-B12RCA MULTIFUNCTION TIMER/COUNTER, 24V INFO484.38387.50
FL1E-B12RCC MULTIFUNCTION TIMER/COUNTER, 120V INFO503.76403.01
FL1E-H12RCA MULTIFUNCTION TIMER/COUNTER, 24V,DISPLAY INFO600.63480.50
FL1E-H12RCC MULTIFUNCTION TIMER/COUNTER, 120V,DISPLAY INFO728.79583.03
FL1E-PG1 MEMORY & BATTERY CARTRIDGE INFO274.73219.78
FL1E-RD1 TEXT DISPLAY FOR FL1 SERIES INFO956.01764.81

Accessories

No accessories found
Features
  • 8 basic plus 31 special function blocks
  • On/off delay, latching, and time delay
  • Four Form C delayed output contacts
  • Space-saving package
  • PI control and dual-stage ramp functions
  • Analog multiplexer
  • Math functions for basic arithmetic operations
  • Password protection
Specifications

Timing Functions:On-delay, off-delay, on/off-delay, retentive, interval, edged triggered, latching relay, current impulse, 7-day time, 12 month time, counter

Time Delay Settings:0.1 sec to 100 hours

Other Functions:See function table

Output:4 Form C relays, SPDT

Contact Rating:10A resistive @ 24 VAC/VDC, 120 and 240 VAC; 3A inductive @ 120 and 240 VAC

Input Voltage:24 VAC/VDC ir 100-240 VAC/VDC (50/60 Hz), depending on model

Operating Temperature:32° to 131℉ (0° to 55℃)

Operating Humidity:10% to 95% RH

Clock Accuracy:±2 sec/day, maximum

Clock Backup:80 hours

Input Points:8 digital

Input Impedance:24 VAC/VDC: 4.8 kΩ; 100-240 VAC/VDC: 840 kΩ

Input ON Time:24 VAC/VDC: 1.5 ms; 100 VAC: 50 ms; 240 VAC: 30 ms, 100 VDC: 25 ms; 240 VDC: 15 ms

Input OFF Time:24 VAC/VDC: 15ms; 100 VAC: 65 ms; 240 VAC: 105 ms; 100 VDC: 95 ms: 240 VDC: 125 ms

Dielectric Strength:2500 VAC, 1min. 500 VDC

Power Consumption:

 : AC 0.9-2.7 VA @ 24 VAC, 1.1-4.6 VA @100 VAC

 :DC 0.4-1.8 W @ 24 VAC, 0.5-2.9 W @ 100 VAC

Display:Optional 48 character, backlit LCD

Mechanical Life:10 million operations

Electrical Life:100,000 operations

Weight:6.7 oz (190 g)

Approvals:UL listed File # E211795, CE, FM approved non-incendive for Class 1, Division II locations

Warranty:1 year

TEXT DISPLAY (sold separately):

Input Voltage:24 VAC, 50/60 Hz, 12 or 24 VDC

Power Consumption:90 mA @ 24 VAC, 40 mA @ 24 VDC, 65 mA @ 12 VDC

Data Transmission:19200 baud

Display:128 columns X 64 rows, LED backlight

Weight:0.5 lb (0.2 Kg)

Warranty: 1 year

Certifications








Download Additional Data

document   Catalog Page
document   Instruction Manual