Supply Voltage:
T30/M30:11-32 VDC (protected against reversal of polarity)
T40/M40:19-32 VAC, 100-140 VAC
Supply VA:
T30/M30:1 VA
T40/M40: 0.9 VA
Signal Output:4-20 mA
Maximum Output :
Impedance:
T30/M30:700Ω @ 24 VDC (= 50 x VDC – 500)
T40/M40:750Ω
Adjustments:Zero/Span adjustments: Non-interactive adjustments by means of 20-turn potentiometers for fine resolution
Accuracy: 1% of range (including non-linearity and hysteresis)
Thermal Effect:Zero ±0.05%/°C; Span ±0.02%/°C
Measurement Range:Upto 10″ WC
Vibration Resistance:5G to 50 Hz
Operating Temperature:32° to 115°F (0° to 45°C)
Storage Temperature:-20° to 160°F (-30° to 70°C)
Media Compatibility:Air, Inert gases
Enclosure:
T30/40:Not rated, Flame retardant, glass-reinforced NORYL
M30/40: (IP65), aluminum alloy #A382
Process Connection:3/16" diameter suitable for 1/8" or 5/32" ID (1/4" OD) Tygon or polyurethane tubing; integral filters at both ports
Wiring Terminations:3/8" terminals, #6 screws
Approvals: CE
Weight:
T30:0.42 lb (0.19 kg)
T40:0.57 lb (0.26 kg
M30:1.27 lb (0.58 kg)
M40:1.2 lb (0.55 kg)
Warranty: 1 year