Supply Voltage:120-600 VAC , 50/60 Hz
System Type:Three-phase (Wye or Delta), or single-phase
Input:0-5A or 0-0.333V
CT Burden:0.75 VA maximum (5A input)
Monitored Voltage:
:Line to Line: 120 to 600 VAC
:Line to Line with potential transformer: 601 to 32000 VAC
Monitored Current:5 to 6000 Amps with current transformer
PT Burden:4.8 VA maximum
Internal Fusing:0.5A, 600V (KLK-0.5)
Pulse Output:Pulsed contact closure for kWh solid-state relay, 50 VAC/VDC maximum, 100 mA maximum
Pulse Rate:Four selectable kWh per pulse rates, 50% duty cycle
Maximum Pulse Rate:Five pulses per second
Digital Output:Maintained contact closure for low-voltage
alarm; 50 VAC/VDC, 100 mA maximum:
Analog Output:Two externally powered 4-20 mA signals selectable for total kW, window kW, peak window kW, total power factor, total kVA, RMS current, or RMS voltage
Maximum Load:725Ω each output @ 24 VDC
Display:** Optional LCD, two lines, 16 characters/line
Accuracy:0.75% of FS (kW, kVA, V, A) ± 0.03 PF (0.4 to 1.0 PF)
Operating Temperature:32° to 122°F (0° to 50°C)
Operating Humidity:5 to 95% (non-condensing)
Dimensions:12"H x 10"W x 4"D (30.5 x 25.4 x 10.2 cm)
:NEMA 3R 20"H x 16"W x 6"D (50.8 x 40.6 x 15.2 cm)
Weight:12 lb (5.5 kg)
:NEMA 3R 43 lb (20 kg)
Approvals:UL and cUL listed, File #E161500 Certified to LonMark Interoperability Guidelines version 3.1
Warranty:18 months