Supply Voltage:24 VAC ± 10% 60Hz
Supply Current:250 mA maximum
Monitored Voltage:
:Line to Line: 120 to 600 VAC
:Line to Line with potential transformer: 601 to 32000 VAC
Monitored Current:5 to 6000A using current transformers
System Type:
2-Wire Single Phase:
:
3-Wire Single Phase:
:
4-Wire Wye:
:
3-Wire Delta:
:
4-Wire Delta:
Communication:
Data Port: Serial interface to EnGenius Desktop Software:
Optional Communications (not field installable):
:BACnet MS/TP
:Lonworks
:Modbus RTU
:N2
Analog Output:
:Quantity 1
:
:Type 4-20 mA (loop powered)
:
:Accuracy 0.5% full scale
:
:Maximum Loop Supply Voltage 30 VDC
:
:Maximum Impedance 850Ω @ 24 VDC
Digital Output:
:Quantity 2
:Type Optically isolated solid state FET switch
:
:Rated Voltage 28 VAC/40 VDC maximum
:Rated Current 100 mA maximum
Operating Temperature:-22° to 158℉ (-30° to 70℃)
Operating Humidity:0 to 95% (non-condensing)
Enclosure:NEMA 4, UL94 rated 5VA
Dimensions:6.5” x 6.5” x 4” (16.5 x 16.5 x 10.1 cm)
Weight:3.1 lb (1.4 kg)
Approvals:ETL, CE, ANSI C12.20
RoHS Statement:Yes
Warranty:1 year