Kele PowerTrak Power Monitoring Interface
The PT-9000 Series Power Monitoring Interface monitors numerous power system parameters for local display and/or remote connection to a BAS or other data acquisition equipment. Any three or single-phase 50/60 Hertz electrical system from 120-600V can be monitored by the PT-9000 Series without the need for potential transformers. Higher voltage systems such as 5 kV or 15 kV services can also be monitored using potential transformers. The PT-9000 Series is available for use with 5A or 0.333V current transformers. Options include a current transformer shorting assembly and a digital LCD display.
Furnished in a NEMA 1 hinged-cover enclosure with external mounting feet and conduit knockouts on all sides, the PT-9000 Series is simple to install. Setup of the PT-9000 Series is easily accomplished with a selector switch and DIP switches. A truly unique feature of the PT-9000 Series is its ability to identify and electronically correct wiring problems such as reversed CT polarities or improper phasing of voltages with CT's.
- Auto-corrects for wiring errors
- Three-phase (Wye or Delta) or single-phase systems
- Voltage selector switch (120-600V)
- Accepts 5A or 0.333V CT's
- Low-voltage alarm contact
- Two 4-20 mA outputs
- Pulse output for KWH with selectable pulse rate
- Optional two-line LCD display
- Optional unique CT shorting assembly
- Easily installed enclosure with external mounting feet
- Optional LonWorks, Modbus, and Metasys communications
Input
System type:Three-phase (Wye or Delta), or single-phase
Input voltage:120-600 VAC
Frequency:50/60 Hz
Input current:0-5A or 0-0.333V
CT primary:5, 50, 75, 100, 150, 200, 250, 300, 400, 500, 600, 750, 800, 1000, 1200, 1500, 1600, 2000, 2500, 3000, 3500, 4000, 5000, or 6000
CT burden:0.75 VA max (5A input)
PT burden:4.8 VA max
Internal fusing:0.5A, 600V (KLK-0.5)
Outputs
Pulse output:Pulsed contact closure for KWH solid-state relay, 50 VAC/DC max, 100 mA max
Pulse rate:Four selectable KWH per pulse rates, 50% duty cycle
Max pulse rate:Five pulses per second
Contact output:Maintained contact closure for low voltage alarm 50 VAC/DC, 100 mA max
Analog outputs:Two externally powered 4-20 mA signals selectable for total KW, window KW, peak window KW, total power factor, total KVA, RMS current*, or RMS voltage*
Max load:725Ω each output @ 24 VDC
Power:External 24 VDC @ 60 mA max
Accuracy:0.75% of F.S. (kW, kVA, V, A); +/-0.03 PF (0.4 to 1.0 PF)
Operating temp:32º to 122ºF (0 to 50ºC)
Humidity:5-95% noncondensing
Display option**:LCD, Two lines, 16 characters/line
Dimensions:12"H x 10"W x 4"D (30.5 x 25.4 x 10.2 cm),
NEMA 3R:20"H x 16"W x 6"D (50.8 x 40.6 x 15.2 cm)
Weight:12 lb (5.5 kg), NEMA 3R: 43 lb (20 kg)
Approvals:UL and ULC listed, File #E161500; Certified to LonMark Interoperability Guidelines version 3.1
Warranty:18 months
* Voltage and current outputs are the average of the three-phase true RMS values.
** When using potential transformers for voltages above 600V, some displayed values must be multiplied by the PT ratio.