455 Voltage Monitors

MotorSaver™ Three-Phase Voltage Monitor

The Model 455 three-phase voltage monitor combines load and line-side monitoring to alert the user of contact failure or impending contact failure. The line-side monitoring will protect the motor from damaging line-side conditions prior to the motor starting. With the Model 455, your motor is fully protected at all times. The motor will not start if a power problem is present.The monitor is equipped with an infrared LED to communicate with the handheld diagnostic tool, the Informer-MS, to display MotorSaver® data to assist in monitoring and troubleshooting the system. Motor run hours, displayed by the Informer-MS can now be reset on the Model 455.


arrow
Features
  • The 455?s universal range from 190-480VAC 50/60 Hz provides the versatility needed to handle global applications.
  • Four adjustment pots provide versatility for a variety of applications.
  • Load and line-side monitoring provides contactor protection.
  • Diagnostic LEDs indicate trip status and provide simple troubleshooting.
  • Microcontroller-based circuitry for better accuracy and higher reliability.
  • Single-phase conditions are detected regardless of regenerated voltages.
  • Transient protection meets IEEE and IEC standards and permits operation under tough conditions.
arrow
Specifications

Supply Watts:6W maximum

Frequency:50*/60 Hz

Contact Rating:SPDT 480 VA @ 240 VAC pilot duty 10A general purpose SPDT high voltage relay (-480R) 470 VA @ 600 VAC pilot duty

Transient Protection:IEC 1000-4-5; 1995 ± 6K1

Line Voltage Monitored:

 :455 190 - 480 VAC

 :455 - 575 475 - 600 VAC

 :455 - 480R 380 - 480 VAC

Low Voltage Trip:90% of setpoint (±1%)

Low Voltage Reset:93% of setpoint (±1%)

Reset Delay Time after Fault:Manual or 2-300 seconds

Reset Delay Time after Power Loss:Manual or 2-300 seconds

Trip Delay Time High Voltage:2-30 seconds, adjustable

Trip Delay Time Low Voltage:2-30 seconds, adjustable

Trip Delay Time Phase Fault:0.5 seconds

Trip Delay Time Unbalance:2-30 seconds, adjustable

Voltage Unbalance Reset:Trip setting minus 1%

Voltage Unbalance Trip:2% to 8%, adjustable

Dimensions:2.9"H x 5.25"W x 2.9"D (7.4 x 13.3 x 7.4 cm)

Weight:0.88 lb (0.396 kg)

Approvals:UL and cUL listed, #E68520, CS1, C1

Warranty:5 years

arrow
Certifications








Step 1 Enter a quantity to select a product or products
Step 2 When done selecting, press Add To Cart. You may save as a Project from the Cart.
arrow
Products

(Wholesale customers, log in for your special pricing.)

QtyModelDescriptionIn StockList PriceInternet Price
455 THREE PHASE LINE-LOAD VOLTAGE MONITOR 190-480VAC INFO310.35248.28
455-480R THREE PHASE LINE-LOAD VOLTAGE MONITOR 390-480VAC INFO442.82354.26
455-575 THREE PHASE LINE-LOAD VOLTAGE MONITOR 475-600VAC INFO310.35248.28
arrow
Accessories
No accessories found