Battery:Two AA 3.6V lithium batteries
Frequency:418 MHz
Transmission Power:1 mW
Range:100 ft
Update Interval:10 to 17 seconds
Analog Input:
:BA/WAI-05 0-5VDC, Impedance > 30KΩ
:BA/WAI-10 0-10VDC, Impedance > 50KΩ
:BA/WAI-420 4-20 mA, Impedance = 100Ω
:BA/WTS Any 10K Type 2 Thermistor, range -40 to 185°F (-40 to 85°C)
Digital Inputs:
:BA/WDI Dry contact
:Note: Contact must be closed for > 20 seconds for detection (< 10Ω closed, >250Ω open)
Operating Temperature:32° to 140°F (0° to 60°C)
Operating Humidity:5 to 95% RH, (non-condensing)
Enclosure:NEMA 4 (IP66)
Dimensions:5.0”H x 4.1”W x 2.5”D (12.7 x 10.4 x 5.4 cm)
Weight:0.5 lb (.22 kg)
Approvals:FCC ID# T4F16963N16964
RoHS Statement:Yes
Warranty:2 year