HM_60, HM_70:
Accuracy:
Humidity:±2% RH (0% to 90% RH) @68°F (20°C)
Temperature:±0.2°C
Supply Voltage:
60 Series: 10 to 35 VDC
70 Series:10 to 35 VDC, 9 to 24 VAC (signal dependant)
Maximum Output :
Impedance:700Ω @ 24 VDC
Minimum Output :
Impedance: 3000Ω min
Measurement Range:
Humidity :
Wall Mount :0 to 95% RH
Duct Mount:0% to 100%
Temperature:
Wall Mount:23° to 131°F (-5° to 55°C)
Duct Mount:-4° to 176°F (-20° to 80°C)
Sensing Technology:Capacative and replaceable, Vaisala HUMICAP® 180
Operating Temperature:
Electronics:23° to 131°F (-5° to 55°C)
Sensor Head (Duct):-4° to 176°F (-20° to 80°C),
Enclosure Rating:Cast aluminum NEMA 4 (IP55), ABS plastic
Wiring Terminations:Screw terminals (20-16 AWG)
Approvals: CE
Weight:
Wall:0.32 lb (0.14 kg)
Duct: 1.68 lb (0.76 kg)
Warranty: 1 year
HM41K:
Sensor :Capacitive and replaceable
Operation :Handheld, onsite calibrator
Reference Probe :
Accuracy:±1% RH (0% to 90% RH)
:±2% RH (90% to 100% RH)
Measuring range :0% to 100% RH,
:-40° to 140°F (-22° to 78°C)
Operating temperature :-40° to 140°F (-40° to 60°C)
Storage temperature :-4° to 140°F (-20° to 60°C)
Temperature coefficient :+0.04% RH/°C typical
Battery :Four AA (LR6) (not included)
Agency approvals :CE, NIST certificate
Weight :2.1 lb (0.95 kg)
Warranty :1 year