Accuracy: 5% (10% to 90%)
Supply Voltage:12-30 VDC, 2.4 VA
Signal Output:4-20 mA/0-5V/0-10V selectable; 0-100% RH
Maximum Output :
Impedance: 700Ω maximum @ 24 VDC
Minimum Output :
Impedance: 10 kΩ minimum
Sensing Technology:Capacitive and replaceable
Operating Humidity:0% to 99%, non-condensing
Operating Temperature:-40° to 140°F (-40° to 60°C)
Enclosure Rating:
Room:ABS plastic, UL94V Room Installed IP20, NEMA 1
Duct/OSA: IP42, NEMA 3R Stainless steel with removable tip, PTFE Teflon® shield
Wiring Terminations:16 to 22 AWG terminals
Approvals: CE
Weight:
Room:0.5 lb. (0.23 kg)
Duct/OSA:1.3 lb. (0.59 kg)
Warranty: 2 years