BAPI Room Duct, and OSA Humidity Transmitters
Model BA/H Series 2% and 3% Accuracy humidity transmitters are designed specifically for HVAC systems. The room transmitters use Delta or BAPI-Stat II enclosures with optional communication jacks. All duct and OSA units come in weatherproof enclosures selectable for NEMA 3R or IP66 applications. All BA/H transmitters have optional temperature sensors or temperature transmitters. Transmitter outputs include 4-20mA, 0-5V ad 0-10V with replaceable sensors.
- Popular room housing
- Accuracies of 2%, 3% or 5%
- Three-year warranty
- Duct and OSA twist-off NEMA 4 housing
- 24 VDC or 24 VAC power (field-selectable)
- 4-20 mA, 0-10V, or 0-5V signal (field-selectable)
- Field calibratable
- Optional temperature sensor
Sensor:Resistive with ceramic sub-straight
Accuracy:2%, or 3%, from 20-95% @ 77ºF (25ºC)
Output:4-20mA or 0-5 V (selectable on certain models) or 0-10 V
Optional temperature sensor
Thermistor (@77ºF/25ºC):1.8 kΩ, 3 kΩ, 3.3 kΩ, 10 kΩ Type 2, 10 kΩ Type 3, 20 kΩ, 50 kΩ, 100 kΩ, 100 Ω
RTD (@32ºF/0ºC):100 Ω 385, 1 kΩ 385, 1 kΩ 275
SC AD592 (@13ºF/-25ºC):247µA
Supply voltage:15-26 VAC/VDC. DC voltage is required for 4-20mA/0-5 V output models
Load impedence
4-20mA:700 Ω maximum @24VDC
0-5 V/0-10 V:10K Ω minimum
Ambient RH
Room:0-100%, non-condensing
Duct/OSA:0-100%
Ambient temperature
Room:32º to 122ºF (0 to 50ºC)
Duct/OSA:-22º to 158ºF (30º to 70ºC)
Filter
Room:Gore-Tex®
Duct/OSA:100 micron sintered stainless steel
Wiring:Four wire, 16 to 22 AWG terminals
Optional display:2.5 digit LCD, adjustable between RH and temperature
Enclosure
Room:ABS Plastic UL94V-0
Duct/OSA
BB:NEMA 4, UV resistant, UL94V-0
WP:Cast aluminum, NEMA 3R
EU:ABS plastic, UL94V-0, IP66
EUO:UV resistant plastic, IP66
Angency approvals:CE, RoHS
Warranty:2 years