Accuracy: ±5% @ 77°F (25°C) from 10% to 95%
Thermal Effect:<0.005% per °F (<0.01 per °C)
Supply Voltage:12-40 VDC or 24 VAC, selectable
Signal Output:4-20 mA, 0-5 VDC, 0-10 VDC (field selectable)
Measurement Range:0% to 100%
Sensing Technology:Capacitive
Operating Temperature:
Room:32° to 122°F (0° to 50°C)
Duct/OSA:-40° to 140°F (-40° to 60°C)
Dimensions:
Room:3.8"H x 2.8"W x 0.9"D (9.8 x 7 x 2.3 cm)
Duct:3.6" (9 cm) Ø head with 8.15"L (20 cm) probe 0.75" (1.9 cm) Ø
OSA:3.6" (9 cm) Ø head with 3.0"L (7.6 cm) probe 1.4" (3.6 cm) Ø
Enclosure:
Room:Plastic Delta-style
Duct/OSA:Plastic weatherproof
Approvals: CE, RoHS