Supply Voltage:18-30 VAC, 50/60 Hz; 0.7W @ 24 VAC; 18-42 VDC
Signal Output:0-5V, 0-10V, or 4-20 mA selectable for CO2, humidity, or temperature (simultaneous current or voltage output for CO2)
Maximum Output :
Impedance: 500Ω
Accuracy:
CO2:
T8100/8300:400-1250 ppm: 3% or 30 ppm, whichever is greater; 1250-2000 ppm: ±5% +30ppm
T8200:10% or 75 ppm, whichever is greater;
Humidity:±2.5% RH (20 to 80% RH)
Temperature:±0.8% @ 72°F (22°C)
Measurement Range:0 to 2000 ppm, 0 to 99% RH (non condensing), 32° to 122°F (0° to 50°C)
Sensing Technology:
CO2:Non-dispersive infrared (NDIR)
Humidity:Capacitive polymer
Temperature:Passive: 10kΩ Type II thermistor
Display: Scrolling LCD
Response Time:5 seconds
Operating Humidity:0% to 100% RH
Operating Temperature:32° to 122°F (0° to 50°C)
Enclosure Rating:UL94-5VA
Approvals: ROHS, CE
Weight: 0.44 lb (0.20 kg)
Warranty: 1 year (lifetime on calibration)
Enclosure: White or black plastic