Supply Voltage:14-27 VDC
Signal Output:Loop powered, 4 to 20 mA, two-wire
Maximum Output :
Impedance: 500Ω max @ 24 VDC
Measurement Range:
CO-1:100 ppm
CO-3:300 ppm
Sensing Technology:Electrochemical
Life Expectancy:> 4 years
Resolution: 1 ppm (models with display only)
Response Time:90%; < 40 seconds @ 77° F (25° C)
Operating Humidity:15% to 90% RH (noncondensing)
Operating Temperature:14° to 104°F (-10° to 40°C)
Enclosure: ABS polymer
Dimensions:3.80″ diameter x 2.13″H (9.65 X 5.41 cm)
Moutning tabs:4.1″ (10.44 cm)
Wiring Terminations:3/4" conduit adapter
Weight: 0.25 lb (0.11 kg)
Warranty: 2 years