Supply Voltage:100 to 240 VAC, 50/60 Hz
Signal Output:3 alarm relays, 1 fault relay, 240 VAC, 3A, and 4-20 mA 500Ω (non-isolated)
Accuracy: ±10 ppm from 25 to 100 ppm or ±10% reading from 100 to 10,000 ppm
Gases Detected:Ammonia (NH3, R-717)
Measurement Range:25-10,000 ppm
Sensing Technology:Single-pass, infrared non-dispersive
Coverage: Up to 50 ft (15m) from measuring point to monitor
Sensitivity: 1 ppm
Warm Up Time:15 minutes
Response Time:9 to 30 seconds depending on sample tube length
Operating Humidity:5% to 90% RH non-condensing
Operating Temperature:32° to 122°F (0° to 50°C)
Dimensions: 7.4"H x 15"L x 3.3"D (18.8 x 38.1 x 8.4 cm)
Approvals: UL (61010A-1), CSA, CE
Weight: 7.0 lb (3.2 kg)
Warranty: 2 years