GE Carbon Dioxide Sensors
The Model 5001 and Model 8041 Carbon Dioxide sensors are designed to monitor the CO2 levels to provide an indication of occupancy for use in demand-controlled ventilation according to ASHRAE Standard 62. Model 5001 wall-mount carbon dioxide sensors are designed to monitor the CO2 concentration in a room. The Model 8041 has a probe to monitor the carbon dioxide inside a duct air stream. Both units output a 0-10VDC signal representing a 0-2000 ppm concentration of CO2.
- Analog output, 0-10 VDC
- ABC Logic(tm) automated calibration
- Non-dispersive infrared technology
- Model 8041 senses in duct air stream
Power:18-30 VAC RMS, 50/60 Hz or 18-42 VDC, polarity protected
Power Consumption:5001-1.75 VA avg, 3.25 VA peak 8041-.65 watts avg, 1.65 watts peak
Range:0-2,000 ppm (factory setting)
Accuracy:5001 +/-100 ppm @ 72ºF (22ºC), 8041 +/-40ppm + 3% reading
8041 duct air velocity:0 to 1500 ft/min (0 to 7.5 m/s)
Temperature dependence:0.1% FS per ºF (0.2% FS per ºC)
Stability:<2% FS over life of sensor
Non-linearity:<1% of FS
Pressure dependence:0.13% of reading per 0.54" W.C. (1mm Hg)
Calibration interval:None, uses ABC Logic (Automatic Background Calibration)
Response time:Estimated at 3-5 minutes for 90% step change
Warm up time:<2 minutes operational, 10 minutes maximum accuracy
Analog output:0-10VDC (1000 ohms output impedance)
Operating temp:32º to 122ºF (0 to 50ºC)
Operating humidity:0% to 95% RH noncondensing
Connections:5001 screw terminals for 18-28 AWG, 8041 leads
Flammability:UL94V-5
Weight
5001:4 oz (0.11 kg)
8041:8 oz (0.23kg)
Certification:FCC Part 15 Class B, CE, ROHS, WEEE
Warranty:2 years