Supply Voltage:24 VAC ±20%, 50/60 Hz, 24 VDC ±20%
Supply Current:150 mA @ 24 VAC, 90 mA @ 24 VDC
Output Signal:0-10 VDC or 4-20 mA; jumper selectable
Loads:0-10 VDC output, 10kΩ minimum resistance; 4-20 mA output, 450Ω maximum resistance
Wiring:Terminal strip with 1/2" NPT conduit connector or M16x1.5 cable gland for 0.18" to 0.39" (0.45 to 10.0 cm) cable diameter
Accuracy:
:EE65 ±40 fpm (0.2 m/s), plus 3% of measured value, at 68℉ (20℃) and 45% RH
:EE66 ±7.9 fpm (0.04 m/s), plus 2% of measured value, at 68℉ (20℃) and 45% RH
Response Time:0.2 or 4 seconds, jumper selectable
Operating Temperature:14° to 122℉ (10° to 50℃), sensing tip can go down to -13℉ (-25℃)
Velocity Range:
:EE65 0-2000 fpm (0-10 m/s), 0-3000 fpm (0-15 m/s) or 0-4000 fpm (0-20 m/s)
:EE66 0-200 fpm (0-1.0 m/s), 0-300 fpm (0-1.5 m/s) or 0-400 fpm (0-2.0 m/s)
Enclosure Rating:NEMA 4 (IP 65)
Dimensions:
:-VB3 3.2"H x 3.2"W x 5.4" (8.0 x 8.0 x 13.7 cm)
:-VB5 3.2"H x 3.2"W x 9.3" (8.0 x 8.0 x 23.7 cm)
Weight:
:-VB3 .25 lb (0.11 kg)
:-VB5 .30 lb (0.14 kg)
Approvals:CE
Warranty:1 year