Supply Voltage:24 VAC ±10%, 50/60 Hz
Supply VA:5 VA
Output Signal:0-10 VDC, 0/4-20 mA
Loads:0-10 VDC output: 1kΩ minimum resistance; 4-20 mA output: 600Ω maximum resistance
Wiring:4.5' (1.4 m) cable from transmitter to probe; screw terminals inside transmitter housing
Accuracy:±5% of measured value plus 0.5% of measuring range
Repeatability:0.5% of measuring range
Temperature Effect:Maximum 0.1%/℃ (0.2%/℉)
Time Constant:63.2% for 3 or 10 seconds
Operating Temperature:Electronics 32° to 122℉ (0° to 50℃); sensing tip -4℉ to 140℉ (-20° to 60℃)
Velocity Range:0-1000 fpm (0.5.1 m/s), 0-2000 fpm (10.2 m/s), or 0-3000 fpm (0-15.3 m/s); DIP switch selectable
Probe Length Range:Adjustable 1" to 8" (2.5 to 20.3 cm)
Enclosure Rating:IP44
Weight:1.8 lb (0.8 kg)
RoHS Statement:Yes
Warranty:1 year