Supply Voltage:10-32 VDC
Maximum Output Impedance:R(load) = 50 (Vs-10)
Output Signal:4-20 mA loop-powered standard (pulse output available special order)
Connections:2200: 1-1/2″ MNPT
:3100: 2″ MNPT
Wiring Terminations:Screw terminals inside housing
Conduit Connection:3/4" FNPT
Configuration:For factory pre-configuration, specify pipe size, pipe material/schedule and maximum flow rate. Separately available Hydro-Flow Field-Pro software is available for field configuration
Accuracy:± 1% of full scale (combined linearity and repeatability)
Display:Optional, LCD alternates between showing 4-digit flow rate and 8-digit total flow
Engineering Units:English, gallons; metric, cubic meters (other units available upon request or can be configured using Hydro-Flow Field-Pro software)
Operating Temperature:-20° to 140℉ (-29° to 60℃)
Velocity Range:1 fps (0.3 mps) minimum, 15 fps (4.5 mps) maximum
Pipe Size Range:2200: 2″ to 20″ (5 to 50 cm)
:3100: 3″ to 20″ (8 to 50 cm)
Installation:Install in straight pipe section with a minimum distance of 10 pipe diameters upstream and 5 pipe diameters downstream to any bend, obstruction or transition
Mounting:Thredolet®, or piping tee (2200 Series only)
Media Compatibility:Water, water/glycol mixtures, condensate
Media Temperature Range:32° to 160℉ (0° to 71℃)
Maximum Pressure:400 psig (2759 kPa) for Thredolet® mount, 150 psig (1035 kPa) for piping tee mount
Materials Of Construction:Reinforced polycarbonate enclosure, Ultem® plastic vortex shedder, 316 SS shedder bar, stainless steel stem, EPDM o-rings, brass compression fitting, aluminum/nickel-plated retractor (3300 Series only)
Enclosure Rating:NEMA 6
Warranty:2 years